Monarch IP – Zinc Coated Steel

An IP66, premium industrial enclosure and switchboard building system designed to be the ultimate in flexibility.

AS/NZS 61439
Monarch IP – Zinc Coated Steel
Australian Made
Australian Made

Product Information

Applications

Designed to be the ultimate in flexibility the Monarch IP system is suitable for small motor control applications, lighting, CT metering and small switchboards (to form 2).

Features

  • IP66 protection rating – more info on IP ratings
  • C rail mountings for equipment
  • Gland plate on all but 175 and 270mm deep enclosures
  • Vertical body and door rails
  • 3 point locking on models of 600mm high and above
  • Lockable L handle on enclosures 1600mm high and above (7mm square key turnbuckle lock on others)
  • Mounting pan is optional extra
  • Region D wind rated to AS1170.2-2002: Structural design actions – Wind actions

Construction

  • 1.6mm thick zinc coated steel
  • 1.6mm steel gland plate (brass also available as an option)
  • Stainless steel hinges and hinge pins for easy door opening
  • Concealed removable hinging
  • Polyurethane gasket (formed in place)
  • Pebble Grey (RAL7032) powdercoated paint finish or,
  • Ripple Orange – X15 (denoted by /RO in the part number code below)

Also available with Viewing Window Doors

DownloadsAccessoriesMore ProductsEnquiryOnline StockistsLocal Stockists

Order Guide

Smaller Enclosures Enclosure Selector Larger Enclosures

Part NumberHeight (mm)Width (mm)Depth (mm)WeightCAD BlocksTemp RiseEnquiry
Standard X15 Orange
IP13132IP13132/RO40040027013Temperature Rise CalculatorEnquiry
IP13212IP13212/RO40060027017Temperature Rise CalculatorEnquiry
IP13214IP13214/RO40060040017Temperature Rise CalculatorEnquiry
IP21132IP21132/RO60040027017Temperature Rise CalculatorEnquiry
IP21212IP21212/RO60060027022Temperature Rise CalculatorEnquiry
IP21214IP21214/RO60060040021Temperature Rise CalculatorEnquiry
IP21292IP21292/RO60080027028Temperature Rise CalculatorEnquiry
IP21294IP21294/RO60080040043Temperature Rise CalculatorEnquiry
IP21295IP21295/RO60080050037Temperature Rise CalculatorEnquiry
IP25254IP25254/RO70070040069Temperature Rise CalculatorEnquiry
IP29212IP29212/RO80060027028Temperature Rise CalculatorEnquiry
IP29214IP29214/RO80060040027Temperature Rise CalculatorEnquiry
IP29215IP29215/RO80060050037Temperature Rise CalculatorEnquiry
IP29216IP29216/RO80060060042Temperature Rise CalculatorEnquiry
IP29294IP29294/RO80080040033Temperature Rise CalculatorEnquiry
IP37212IP37212/RO100060027033Temperature Rise CalculatorEnquiry
IP37254IP37254/RO100070040033Temperature Rise CalculatorEnquiry
IP37294IP37294/RO100080040040Temperature Rise CalculatorEnquiry
IP45212IP45212/RO120060027038Temperature Rise CalculatorEnquiry
IP45214IP45214/RO120060040028Temperature Rise CalculatorEnquiry
IP45215IP45215/RO120060050050Temperature Rise CalculatorEnquiry
IP45216IP45216/RO120060060056Temperature Rise CalculatorEnquiry
IP45294IP45294/RO120080040051Temperature Rise CalculatorEnquiry
IP45295IP45295/RO120080050060Temperature Rise CalculatorEnquiry
IP61214IP61214/RO160060040045Temperature Rise CalculatorEnquiry
IP61215IP61215/RO160060050064Temperature Rise CalculatorEnquiry
IP61216IP61216/RO160060060070Temperature Rise CalculatorEnquiry
IP61294IP61294/RO160080040054Temperature Rise CalculatorEnquiry
IP61295IP61295/RO160080050076Temperature Rise CalculatorEnquiry
IP69214IP69214/RO180060040057Temperature Rise CalculatorEnquiry
IP69215IP69215/RO180060050070Temperature Rise CalculatorEnquiry
IP69294IP69294/RO180080040069Temperature Rise CalculatorEnquiry
IP69295IP69295/RO180080050083Temperature Rise CalculatorEnquiry
IP77135IP77135/RO200040050083Temperature Rise CalculatorEnquiry
IP77136 IP77136 /RO200040060079.9Temperature Rise CalculatorEnquiry
IP77214IP77214/RO200060040063Temperature Rise CalculatorEnquiry
IP77215IP77215/RO200060050077Temperature Rise CalculatorEnquiry
IP77216IP77216/RO200060060084Temperature Rise CalculatorEnquiry
IP77218IP77218/RO2000600800119.6Temperature Rise CalculatorEnquiry
IP77294IP77294/RO200080040076Temperature Rise CalculatorEnquiry
IP77295IP77295/RO200080050091Temperature Rise CalculatorEnquiry
IP77296IP77296/RO200080060099Temperature Rise CalculatorEnquiry
IP77298IP77298/RO2000800800109Temperature Rise CalculatorEnquiry

Smaller Enclosures Enclosure Selector Larger Enclosures

Accessories

Accessories

  • Lock options such as L handle
  • Metal mounting pans
  • Insulated mounting pans
  • Double hinged insulating panels
  • Hinged escutcheons
  • Fixed escutcheons
  • Gland plates
  • Shelves
  • Plinths
  • Rainhood
  • Vent kit (IPVK)
  • Vent hoods
  • Lifting brackets
  • Wall mounting brackets
  • Rails (‘C’, DIN, UV, escutcheon and busbar)
  • Climate control equipment

Climate Control

For more information see our Climate Control page (opens in new tab)

Lock Options

Standard

Catalogue No.TypeMaterialCommentsLock Insert TypeKeyImage
IP020TurnbuckleChromed SteelStandard7mm Square Chromed SteelSKZTurnbuckle Lock - 7mm square, chrome steel
IP050L Handle - LockableChromed SteelStandard 1600mm or higher, Option less than 1600mmKey Code 92268SK3L Handle Lockable - Chrome Steel Key 92268

Options

Catalogue No.TypeMaterialCommentsLock Insert TypeKeyImage
IP030Wing Knob - LockableOptionKey Code 92268SK3Lockable Wing Knob - 92268 Key
IP030/CL001Wing Knob - LockableOptionKey Code CL001SK3Lockable Wing Knob - 92268 Key
IP030/L003Wing Knob - LockableOptionKey Code L003SK3Lockable Wing Knob - 92268 Key
IP111Wing Knob - Non-lockableOptionNon-lockable Wing Knob
IP040T Handle - LockableChromed SteelOptionKey Code 92268SK3T Handle Lockable - Chromed Steel 92268 Lock
IP050L Handle - LockableChromed SteelStandard 1600mm or higher, Option less than 1600mmKey Code 92268SK3L Handle Lockable - Chrome Steel Key 92268
IP052L Handle - PadlockableChromed SteelOptionPadlockL Handle - Padlockable, Chrome Steel
IP060Swing Handle - PadlockableChromed SteelOptionPadlockSwing Handle - Padlockable Chrome Steel
Inserts for Turnbuckle Locks - Optional
Catalogue No.ProductMaterialLock Insert TypeKey
LKINS3PInsertSteel3mm Double Bit PinSKZ
LKINS8SInsertSteel8mm SquareSK8
LKINS8TInsertSteel8mm TriangleSKZ

AS/NZS 61439 Compliance

AS/NZS 61439 is the new series of standards for low-voltage (LV) switchgear and control gear assemblies. For more information on whether you need to comply see our AS/NZS 61439 page.

Click the bar below the requirements and responsibilities for complaince with AS/NZS 61439 for this enclosure.

The following definitions apply to this table: -

  • Original Manufacturer* - Switchboard designer and manufacturer of the switchboard enclosure.
  • Assembly Manufacturer* - A switchboard builder.
  • Original Equipment Manufacturer - The company who manufactured the switchgear used in final assembly.

*The original manufacturer and assembly manufacturer can be the same company or different companies.

If you are a SWITCHBOARD BUILDER this means you are the ASSEMBLY MANUFACTURER and you may be the ORIGINAL MANUFACTURER too. Any switchgear you order will need to be covered by the requirements of the Original Equipment Manufacturer.

B&R has some (but not all) of the responsibilities of the ORIGINAL MANUFACTURER.

If you are an END USER of the equipment you can see who has responsibility from these definitions.

NoCharacteristic to be CheckedClauseResponsibilityComments
Resistance to corrosion  10.2.2PassedThe resistance to corrosion was tested using a representative samples. Report; 103687.
Thermal stability (relates to non-metal enclosures)  10.2.3.1N/AThis clause refers mainly to plastic enclosures.
Resistance to abnormal heat and fire (due to internal electric effect)  10.2.3.2PassedAll insulating materials supplied have been tested to 960ºC glow-wire Standard. Plus ES report;
103863
Resistance to ultra-violet (UV) radiation  10.2.4PassedUV ratings refer mainly to plastic enclosures however metal Powder-coat painted enclosures incorporates UV stabilization. AkzoNobel report; 20LSR178
Lifting  10.2.5PassedLifting is verified by test, if required. Generally this relates to larger switchboards to which lifting means (lugs) have been provided. Plus ES report; 103687
Mechanical Impact  10.2.6PassedIK10; Metal enclosure systems have been tested to exceed IK10 (20 Joules).
Marking  10.2.7AssemblerMarkings must be verified by test. Tests are performed by rubbing with water and petroleum spirits; generally done by the Switchboard Builder (Assembler).
2Degree of protection of enclosures (IP)10.3Passed / Plus ES2IP66; Ingress Protection (IP) rating needs to be verified by test or by assessment. Plus ES report; 103687
3Clearances10.4AssemblerClearance and creepage can only be verified by test. Switchboard Builders (Assembler) must maintain compliance by ensuring correct clearance and creepage distances are maintained at >8mm (Uimp=8kV) and >16mm (Ui=1kV) 4 Creepage distances 10.4 respectively
4Creepage distances10.4Assembler
5Protection against electric shock and integrity of protective circuits10.5
Effective continuity between the exposed conductive parts of the ASSEMBLY and the protective circuit   10.5.2Passed / Plus ES2Equipotential protective earth bonding points are required to be verified by test to less than 0.1ohm. Similar enclosure designs have been tested by Plus ES report; 103687
Short-circuit withstand strength of the protective circuit   10.5.3Passed / Plus ES2Protective circuit verification can be by test or comparison with a reference design. Plus ES report; 103687.
6Incorporation of switching devices and components10.6AssemblerPoints 6, 7 and 8 are largely the responsibility of the Switchboard builder (Assembler). It is a requirement that the Assembler follow guidance from the original manufacturer. The advice of original manufacturers such as B&R and switchgear manufacturers, needs to be adhered to. Switchboard Builders need to be aware of the Standard’s requirements for these verification points and incorporate these into complete design verification documentation.
7Internal electrical circuits and connections10.7Assembler
8Terminals for external conductors10.8Assembler
9Dielectric Properties10.9
Power-frequency withstand voltage  10.9.2Passed / Plus ES2Dielectric properties have been tested as per Plus ES report; 103687.
Impulse withstand voltage  10.9.3
10Temperature-rise limits10.1Designer or AssemblerTemperature-rise can be determined by test or by comparison or by calculation. Temperature rise methods provided in AS/NZS 60890 can be used for switchboards not exceeding 1600A rating. Designers need to use AS/NZS 60890 for Monarch IP Series of enclosures with a rating not exceeding 1600A. Higher ratings need to be referred to B&R. Plus ES report: 103814.
11Short circuit withstand strength10.11Passed / Plus ES2Monarch IP low-voltage switchboards are designed and tested in full compliance with AS/NZS 61439 and have been externally verified to withstand 50kA rms for 3s.
12Electromagnetic compatibility (EMC)10.12AssemblerEquipment installed in switchboards shall comply with the immunity requirements of the relevant product or generic EMC standard. The Switchboard builder (assembler) shall obtain from the device and or component manufacturer the specific performance criteria of the equipment based on the acceptance criteria given in the relevant standard.
13Mechanical operation10.13AssemblerThis verification testing need NOT be done on devices already been type tested according to their relevant product standard. Only if their mechanical operation has been modified does the assembly need to be retested by cycling it 200 times.